RCMB132-01

    The AC/DC sensitive residual current monitoring module monitors electrically earthed power supplies up to 300 V and connected loads up to nominal currents of 32 A for leakage and fault currents.

    The module is intended for installation in distribution equipment such as PDUs (Power Distribution Units), outlet boxes or multiple socket-outlets and is supplied with DC 12…24 V.

    The RCMB132-01 is designed for installation in PDUs and outlet boxes. The module can communicate with a master via an RS-485 interface via Modbus RTU. It is possible to connect several devices in a daisy chain. For this purpose, the RCMB132-01 provides two identical connectors for RS-485 (incl. power supply).

    • Функции
    • Применения
    • Комплектующие
    • Спецификация для заказа
    • Загрузки
    • AC/DC sensitive leakage and fault current monitoring for preventive maintenance
    • High resolution for implementing equipment leakage current monitoring
    • Measured value and alarm transmission via Modbus RTU (RS-485)
    • Frequency range DC…2 kHz
    • Compact design for monitoring nominal loads up to In = 32 A
    • Low load current sensitivity due to fully shielded measuring current transformer
    • Continuous monitoring of the connection to the measuring current transformer
    • Integrated test function
    • Supply voltage DC 12…24 V

       

      Дополнительные комплектующие для RCMB132-01

      TypeArt. No.
      Mounting foot MCCT20 B91080111

      Copyright MAXXmarketing GmbH